omron — Frequency Arrival Signal

4-2 Function Mode 4 Signal During RUN This function outputs a signal while the Inverter is running. Functions •Also outputs a signal during DC injection braking. Below is the time chart. Frequency Arrival Signal This function outputs a signal when the output frequency has reached the set value. •For elevating machines, use this signal for applying the brake. 4-63 Data Description Reference item Page 07 FBV: PID FB status output PID FB status output 4-67 08 NDc: Network error Network error 4-68 09 LOG: Logic operation output Logic operation result output 4-69 10 ODc: Do not use. — — 43 LOC:

Light load detection signal Light load detection signal 4-70 Data Symbol Function name Status Description 00 RUN Signal during RUN ON The Inverter is in RUN mode. OFF The Inverter is in STOP mode. Available input terminals P1-PC, MA-MC (or MB-MC) Required settings C021, C026 Output frequency FW RUN output Data Symbol Function name Status Description 01 FA1 Constant speed arrival signal ON The Inverter output frequency has reached the F001 set value. OFF The Inverter output frequency has fallen below the F001 set value. 02 FA2 Over set frequency arrival signal ON The Inverter output frequency has exceeded the C042 set value during acceleration.

OFF The Inverter output frequency has fallen below the C042 set value during acceleration. Available input terminals P1-PC, MA-MC (or MB-MC) Required settings C021, C026, C042, C043