omron — Frequency Arrival Signal

4-2 Function Mode •Below is the hysteresis of the frequency arrival signal: ON: (Set frequency - 1% of the maximum frequency) (Hz) OFF: (Set frequency - 2% of the maximum frequency) (Hz) 4 „ Constant Speed Arrival Output (01: FA1) •Outputs a signal when the output frequency has reached the level set in the frequency setting (F001, A020, and A220) or multi-step speed reference (A021 to A035). Functions Output frequency f on f off Set frequency f on :1% of the max. frequency f off :2% of the max. frequency (Example)(Max.

frequency fmax = 120 (Hz) Set frequency fset = 60 (Hz) foff = 120Ч0.02 = 2.4 (Hz) fon = 120Ч0.01 = 1.2 (Hz) FA1 During deceleration:OFF at 60 - 2.4 = 57.6 (Hz) During acceleration:ON at 60 - 1.2 = 58.8 (Hz) „ Output Over Set Frequency (02: FA2) •Outputs a signal when the output frequency has exceeded the arrival frequencies during acceleration/deceleration set in [C042, C043 (FA2)]. C043 f on :1% of the max. frequency f off :2% of the max. frequency Output frequency C042 f on f off FA2 4-64 Parameter No. Function name Data Default setting Unit C042 Arrival frequency during acceleration 0.0: Does not output arrival signal during acceleration 0.1 to 400.0:

Outputs arrival signal during acceleration 0.0 Hz C043 Arrival frequency during deceleration 0.0: Does not output arrival signal during deceleration 0.1 to 400.0: Outputs arrival signal during deceleration 0.0 Hz