3-7 Parameter List 3 Operation * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. 3-33 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Multi-function output setting C021 Multi-function output terminal P1 selection 00: RUN (signal during RUN) 01: FA1 (constant speed arrival signal) 02: FA2 (over set frequency arrival signal) 03: OL (overload warning) 04: OD (excessive PID deviation) 05: AL (alarm output) 06: Dc (disconnection detection) 07: FBV (PID FB status output) 08: NDc (network error) 09: LOG(logic operation output) 10: ODc (Do not use.) 43:
LOC (light load detection signal) 00 No ⎯ 4-62 C026 Relay output (MA, MB) function selection 05 C028 AM selection 00: Output frequency 01: Output current 00 No ⎯ 4-35 4-75 C031 Multi-function output terminal P1 contact selection 00: NO contact at MA; NC contact at MB 01: NC contact at MA; NO contact at MB 00 No ⎯ 4-71 C036 Relay output (MA, MB) contact selection 01 C038 Light load signal output mode 00: Enabled during acceleration/deceleration/ constant speed 01: Enabled only during constant speed 01 No ⎯ 4-70 C039 Light load detection level 0.0 to 2.0 × Rated current (0.0 setting: Function disable) Rated current No ⎯ 4-70 Level output status setting C041 Overload warning level 0.0:
Does not operate 0.1 × Rated current to 2.0 × Rated current Rated current No A 4-31 4-65 C241 *2nd overload warning level Rated current C042 Arrival frequency during acceleration 0.0 to 400.0 0.0 No Hz 4-64 C043 Arrival frequency during deceleration 0.0 to 400.0 0.0 No Hz 4-64 C044 PID deviation excessive level 0.0 to 100.0 3.0 No % 4-20 4-65 C052 PID FB upper limit 0.0 to 100.0 100 No % 4-20 C053 PID FB lower limit 0.0