‹ Applicable Wire Gauges and Closed-Loop Connectors Select the appropriate wires and crimp terminals listed in Table 2.1 through Table 2.3 . Table 2.1 200 V Class Wire Gauges * 1. Connect the momentary power loss compensation unit. * 2. Normally not used. * 1, * 2 Do not connect the power to these terminals. Table 2.2 400 V Class Wire Gauges * 1. Connect the Momentary Power Loss compensation unit. * 2. Normally not used. * 1, *2 Do not connect power to these terminals.
2 -6 MxC Model CIMR- Terminal Symbol Terminal Screws Tightening Torque (N•m) Possible Wire Gauges mm2(AWG) Recom- mended Wire Gauge mm2 (AWG) Wire Type ACA25P5 R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 M5 2.5 Nm 8 to 14 (8 to 6) 8 (8) Power cables, e.g., 600 V vinyl power cables r2*2, s2*2, t2*2, p1*1, n1*1 M4 1.3 to 1.4 Nm 2 to 3.5 (14 to 12) 2 (14) M8 9 to 10 Nm 5.5 to 22 (10 to 4) 5.5 (10) ACA2011 R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 M5 2.5 Nm 14 (6) 14 (6) r2*2, s2*2, t2*2, p1*1, n1*1 M4 1.3 to 1.4 Nm 2 to 3.5 (14 to 12) 2 (14) M8 9 to 10 Nm 8 to 22 (8 to 4) 8 (8) ACA2022 R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 M8 9 to 10 Nm 38 (1) 38 (1) r2*2, s2*2, t2*2, p1*1, n1*1 M4 1.3 to 1.4 Nm 2 to 3.5 (14 to 12) 2 (14) M8 9 to 10 Nm 14 to 38 (6 to 2) 14 (6) MxC Model CIMR- Terminal Symbol Terminal Screws Tightening Torque (N•m) Possible Wire Gauges mm2 (AWG) Recom- mended Wire Gauge mm2 (AWG) Wire Type ACA45P5 R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 M5 2.5 Nm 5.5 to 14 (10 to 6) 5.5 (10) Power cables, e.g., 600 V vinyl power cables r2*2, s2*2, t2*2, p1*1, n1*1 M4 1.3 to 1.4 Nm 2 to 3.5 (14 to 12) 2 (14) M8 9 to 10 Nm 2 to 22 (14 to 4) 2 (14) ACA4011 R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 M5 2.5 Nm 8 to 14 (8 to 6) 8 (8) r2*2, s2*2, t2*2, p1*1, n1*1 M4 1.3 to 1.4 Nm 2 to 3.5 (14 to 12) 2 (14) M8 9 to 10 Nm 5.5 to 22 (10 to 4) 5.5 (10) ACA4022 R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 M8 9 to 10 Nm 22 to 38 (4 to 1) 22 (4) r2*2, s2*2, t2*2, p1*1, n1*1 M4 1.3 to 1.4 Nm 2 to 3.5 (14 to 12) 2 (14) M8 9 to 10 Nm 8 to 38 (8 to 2) 8 (8)