User Manual of EM730 Series Inverter parameter correctly according to the actual situation. The EM730 series inverter supports asynchronous and synchronous motors. Please set this 167 code name setting address F01.00 Motor type 0: ordinary asynchronous motor 1: variable-frequency asynchronous motor 2: permanent magnet synchronous motor 0 〇 0x0100 Function code Function code name Parameter description Unit Default setting Attribute mailing address F01.01 Rated power of electric motor 0.10~650.00 kW Depending on the motor type 〇 0x0101 F01.02 Rated voltage of motor 50~2000 V Depending on the motor type 〇 0x0102 F01.03 Rated current of motor 0.01 to 600.00 (rated power of motor:
≤75 kW) 0.1 to 6000.0 (rated power of motor: > 75 kW) A Depending on the motor type 〇 0x0103 F01.04 Rated frequency of motor 0.01~600.00 Hz Depending on the motor type 〇 0x0104 F01.05 Rated speed 1~60000 rpm Depending on the motor type 〇 0x0105 F01.06 Motor winding connection 0:Y 1:Δ Depending on the motor type 〇 0x0106 F01.07 Rated power factor of motor 0.600~1.000 Depending on the motor type 〇 0x0107 F01.08 Motor efficiency 30.0~100.0 % Depending on the motor 〇 0x0108