User Manual of EM730 Series Inverter M1 is a multi-function analog output terminal. Its functions can be defined separately by setting the value of the function code F03.21. “operating frequency (absolute value)”. The current |operating frequency| is reflected by the For example, if F03.21=0 is defined, the function of the M1 terminal is to output the output voltage. If the operating frequency increases from 0.00Hz to 50.00Hz (assuming F00.16=50.00), the voltage of the M1 output port will increase from 0.00V to 10.00V under the default conditions, showing the same change trend. Specific options are described in Table 7-9.
Table 7- 9 Function List of Multi-function Analog Output Terminal 195 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F03.21 Options of analog output M1 See Table 7-9 Function List of Multi-function Analog Output Terminal 0 〇 0x0315 Settings Function Description 0 Operating frequency (absolute value) 0.00Hz to Fmax, corresponding to the output 0.0% to 100.0% 1 Set frequency (absolute value) 0.00Hz to Fmax, corresponding to the output 0.0% to 100.0% 2 Output torque (absolute value) 0.0% to 200.0%, corresponding to the output 0.0% to 100.0% 3 Set torque (absolute value) 0.0% to 200.0%, corresponding to the output 0.0% to 100.0% 4 Output current 0.0A to 2*Ie, corresponding to the output 0.0% to 100.0% 5 Output voltage 0.0V to 1.5*Ue, corresponding to the output 0.0% to 100.0% 6 Bus voltage 0V to about 2.63*Ue, corresponding to the output 0.0% to 100.0% (That is, for the 220V driver, 579V corresponds to the output 100.0%; and for the 380V driver, 1000V corresponds to the output 100.0%.
Drivers at different voltage levels have the same output voltage at their rated voltages.) 7 Output power 0.00kW to 2*Pe, corresponding to the output 0.0% to 100.0% 8 AI1 Output the actual input voltage, instead of the offset