User Manual of EM730 Series Inverter The function of protection retry is to prevent the impact of occasional protection on the normal operation of the system. This is valid only for protections of F07.18, F07.32 and F07.36. is, the protection will be reset. The protection status depends on F07.15 and the output of the digital output terminal. If a fault is still detected after the protection retry interval, the protection If protection retry is enabled, this will be performed after a corresponding protection. That retry will be continued to the set number of protection retries (F07.14) and then the corresponding protection will be reported.
If the fault is not detected after several protection retries, the protection retries will be deemed successful and the inverter will continue to run normally. When protection retries succeed and no trip protection is enabled within the recovery time (F07.17), the number of protection retries will be cleared. When a protection is enabled again, 224 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F07.14 Protection retries 0-20; 0:disable protection retry 0 〇 0x070E F07.15 Options of digital output action in protection retries 0: no action 1:
action 0 〇 0x070F F07.16 Interval of protection retries 0.01 ~ 30.00 s 0.50 ● 0x0710 F07.17 Restoration time of protection retries 0.01 ~ 30.00 s 10.00 ● 0x0711 F07.18 Action option of protection E07 * E02 E06 E05 E04 0 *0000 〇 0x0712 0: allow protection retry 1: disable protection retry F07.32 Action option 2 of protection E10 E13 E15 E16 * E19 E20 * 000 00000 〇 0x0720 0: allow protection retry 1: disable protection retry F07.36 Action option 3 of protection * * * * * * E09 E17 *****00 〇 0x0724 0: allow protection retry 1: disable protection retry