sinee — 7.8F07 protection parameter group

User Manual of EM730 Series Inverter protection retries will be performed from zero. In case of any trip protection within this period, protection retries will be carried out based on the last count. With regard to some protections, the action mode of the inverter can be selected via this function code. The inverter will stop running freely when the corresponding bit is set to 0 and according to the stop mode (F04.19) when the corresponding bit is set to 1. These two function codes are subject to bit operation. You only need to set the corresponding bit to 0 or 1. As shown in the table below: Table 7-11 Detailed Definition of Protection Action Bits For example:

To stop the inverter according to the stop mode (F04.19) after the E08 and E13 protection is enabled, you only need to set the 1 st bit corresponding to E08 and the 3 rd bit corresponding to E13 to 1. That is, F07.19=xxx x1x1x. When the off-load protection is valid (F07.21=1), the inverter will be in the running status without DC braking, and the output current is below the off-load detection level (F07.22) and maintained for the off-load detection time (F07.23), the inverter will be in the off-load status.

225 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F07.19 Action option 1 of protection E21 E16 E15 E14 E13 * E08 E07 000 00*00 〇 0x0713 0: free stop 1: stop according to stop mode F07.20 Action option 2 of protection E28 E27 * E23 00*0 〇 0x0714 0: free stop 1: stop according to stop mode F07.19 E21 E16 E15 E14 E13 * E08 E07 F07.20 * * * * E28 E27 * E23 Correspond ing bit 7 6 5 4 3 2 1 0 Settings 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F07.21 Options of load loss protection 0: invalid 1:

valid 0 ● 0x0715 F07.22 Load loss detection level 0.0~100.0 % 20.0 ● 0x0716 F07.23 Load loss detection time 0.0~60.0 s 1.0 ● 0x0717 F07.24 Options of load loss protection action 0: trip protection, free stop 1: trip protection, stop according to stop mode 2: continue to run, with DO status output 1 〇 0x0718