User Manual of EM730 Series Inverter The compensation mode 1 is often selected. If the motor is prone to oscillation at high power and under VF control, the compensation mode 2 may be selected. In the terminal control mode (F00.02=1), this function code is used to set the highest priority of the jog command. If the terminal jog priority is valid (F15.39=1), the running status can be switched to jog running in the presence of a valid jog terminal; and if the terminal jog priority is invalid (F15.39=0), the running status cannot be directly switched to jog running. Set the acceleration and deceleration time during rapid stop. Current reached:
In the running state, the output current > the current reaches the tested value (F15.44), and the current output is valid. In the Non-running state, the output current ≤ current to test value (F15.44) - CDT 285 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F15.39 Terminal jog priority 0: invalid 1:
valid 0 〇 0x0F27 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F15.40 Deceleration time for quick stop 0.00 ~ 650.00 (F15.13=0) 0.0 ~ 6500.0 (F15.13=1) 0 ~ 65000 (F15.13=2) s 1.00 ● 0x0F28 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F15.55 The current reaches the measured value 0.0~300.0(100.0% corresponding to rated motor current) % 100 ● 0x0F37 F15.56 The current reaches the hysteresis 0.0~F15.44 % 5 ● 0x0F38 F15.57 Torque reaches test value 0.0~300.0(100.0% corresponding to rated motor torque) % 100 ● 0x0F39 F15.58 The torque reaches the hysteresis ring 0.0~F15.46 % 5 ● 0x0F3A