User Manual of EM730 Series Inverter hysteresis (F15.45), the current output is invalid; Otherwise, the current output status does not change. The terminal remains in the upper state between the current reaching the tested value (F15.44) - CDT hysteresis (F15.45) and the current reaching the tested value (F15.44). Torque reached: In the running state, | the output torque | is greater than | the torque reaches the tested value (F15.44) |, the current output is valid.
the tested value (F15.44) | - the TDT hysteresis (F15.47), the current output is invalid; In the Non-running state, | the output torque | is less and equal than | the torque reaches Otherwise, the current output status does not change. The terminal remains in the upper state between torque arrival test value (F15.46) - TDT hysteresis (F15.47) and torque arrival test value (F15.46). Speed reached : In the acceleration state, the output frequency is greater than the speed reaching the rising limit (F15.63), and the current output is valid; In the deceleration state, the output frequency is less than the speed reaches the descent limit (F15.65), and the current output is invalid.
the delay of output terminal action. Increasing F15.64 can increase anti-interference ability, prevent misoperation, and increase 286 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F15.62 PG card feedback frequency display filtering time 0~20000 ms 300 ● 0x0F3E F15.63 The speed reaches the limit of rise 0.00~Fmax Hz 30 ● 0x0F3F F15.64 The speed reaches filtering time 0~60000 ms 500 ● 0x0F40 F15.65 The speed reaches the limit of descent 0.00~Fmax Hz 0 ● 0x0F41