User Manual of EM760 High-Performance Inverter 281 F00.23 Carrier frequency 1.0-16.0 (rated power of the inverter: less than 4kW) 1.0-10.0 (rated power of the inverter: 5.5- 7.5kW) 1.0 - 8.0 (rated power of inverter 11 - 45kW) 1.0 - 4.0 (rated power of inverter 55 - 90kW) 1.0 - 3.0 (rated power ofinverter 110 - 560kW) kHz 2.0 ● 0x0017 F00.24 Automatic adjustment of carrier frequency 0: Invalid 1: valid 1 2: valid 2 1 O 0x0018 F00.25 Noise suppression of carrier frequency 0: Invalid 1: Noise suppression mode 1 of carrier frequency 2: Noise suppression mode 2 of carrier frequency 0 O 0x0019 F00.26 Noise suppression width 1~20 1 ● 0x001A F00.27 Noise suppression intensity 0-10:
Noise suppression mode 1 of carrier frequency 0-4: Noise suppression mode 2 of carrier frequency 0 ● 0x001B F00.28 Options of motor parameter group 0: parameter group of motor 1 1: parameter group ofmotor 2 0 O 0x001C F00.29 User password 0~65535 0 O 0x001D F00.30 Model selection 0: G type 1: P type 0 O 0x001E F00.31 Frequency resolution 0: 0.01Hz; 1: 0.1Hz (speed unit: 10rpm) 0 O 0x001F F00.32 Frequency point corresponding to the lower limit of carrier frequency 0.00~F0.33 Hz 20.00 O 0x0020 F00.33 Frequency point corresponding to the upper limit of carrier frequency 10.00~150.00 HZ 50.00 O 0x0021 F00.34 Lower limit of carrier frequency 1.0~F00.23 kHz 2.0 O 0x0022