sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 282 F00.35 Inverter supply voltage selection 0: 380V 1: 440V 2: 480V 3: 600V 4: 690V 0 O 0x0023 F00.36 Start/stop channel selection for communication control 0: Modbus 1: Profinet 2: EtherCAT 3: CANopen 10: All protocols are valid 0 O 0x0024 F00.37 Communication- specific channel selection 0 O 0x0025 F00.38 Parameter locking function selection 0: Locked for all command channels 1: Only the keyboard locked 0 O 0x0026 F00.39 Single-brush and double-brush PWM switch control 0: Single-brush 1: Double-brush 2: Automatic switch 0 O 0x0027 F01 Parameter group of motor 1 F01.00 Motor type 0: ordinary asynchronous motor 1:

variable-frequency asynchronous motor 2: permanent magnet synchronous motor 0 O 0x0100 F01.01 Rated power of electric motor 0.10~650.00 kW Depending on the motor type O 0x0101 F01.02 Rated voltage of motor 50~2000 V Depending on the motor type O 0x0102 F01.03 Rated current of motor 0.01 to 600.00 (rated power of motor: ≤75 kW) 0.1 to 6000.0 (rated power of motor: > 75 kW) A Depending on the motor type O 0x0103 F01.04 Rated frequency of motor 0.01~600.00 Hz Depending on the motor type O 0x0104 F01.05 Rated speed 1~60000 rpm Depending on the motor type O 0x0105 F01.06 Motor winding connection 0: Y 1: Δ Depending on the motor type O 0x0106