User Manual of EM760 High-Performance Inverter F00.03=0: the terminal RUN is in the running status, and F/R in the forward/reverse status. The terminal RUN is activated/deactivated to control the start and stop of the inverter; terminal F/R is activated/deactivated to control the forward/reverse running. When the mode of deceleration to stop is selected, the logic diagram is as shown in the figure (b) below; F00.03=1: the terminal RUN controls forward running, and the terminal F/R is in the reverse mode. Enable/Disable the terminal RUN to control the forward running and stop of the inverter, and the terminal F/R to control the reverse running and stop.
When the terminals RUN and F/Rare enabled simultaneously, the inverter will be stopped. When the mode of deceleration to stop is selected, the forward/reverse logic is as shown in the figure (d) below; (a) Wiring diagram of two-line control (F00.03=0) (b) F04.19=0, F00.03=0,run the forward/reverse logic (c) Wiring diagram of two-line control (F00.03=1) (d) F04.19=0, F00.03=1: forward/reverse running logic Fig. 6-1 Two-line control When the start/stop value ofF00.03 is set to 0 or 1, even ifthe terminal RUN is available, the inverter can be stopped by pressing the STOP key or sending an external stop command to the terminal.
In this case, the inverter will not be in the running status until the terminal RUN is disabled and then enabled. Three-line control: F00.03=2: the terminal RUN controls forward running, the terminal Xi is for stop, and the terminal F/R is in the reverse status. The terminal RUN is normally ON for forward running, and the terminal F/R is normally ON for reverse running, with valid pulse edges. The terminal Xi is normally closed for stop, with the valid level. When the inverter is in the running status, press Xi to stop it. When the mode of deceleration to stop (F04.19=0) is selected, the logic diagram is as shown in figure (b) below.
The terminal Xi is for “three-line running and stop control” as defined by F02.00 to F02.04. 74