Appendix-1 Parameter List Appendix * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. App-9 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value Operation frequency A141 Operation frequency input A setting 00: Digital Operator (F001) 01: Digital Operator (FREQ adjuster) 02: Input FV 03: Input FI 04: RS485 communication 02 No A142 Operation frequency input B setting 03 No A143 Operator selection 00: Addition (A + B) 01: Subtraction (A - B) 02:
Multiplication (A × B) 00 No Frequency addition A145 Frequency addition amount 0.0 to 400.0 0.0 Yes Hz A146 Frequency addition direction 00: Adds A145 value to output frequency 01: Subtract A145 value from output frequency 00 No VR adjustment A151 VR start frequency 0.0 to 400.0 0.0 No Hz A152 VR end frequency 0.0 to 400.0 0.0 No Hz A153 VR start ratio 0. to 100. 0. No % A154 VR end ratio 0. to 100. 100. No % A155 VR start selection 00: Use start frequency [A151] 01: 0 Hz start 01 No Restart after momentary power interruption b001 Retry selection 00: Alarm 01: 0 Hz start 02: Frequency matching start 03:
Trip after frequency matching deceleration stop 00 No b002 Allowable momentary power interruption time 0.3 to 25.0 1.0 No s b003 Retry wait time 0.3 to 100.0 1.0 No s b004 Momentary power interruption/ undervoltage trip during stop selection 00: Disabled 01: Enabled 00 No b005 Momentary power interruption retry time selection 00: 16 times 01: No limit 00 No