omron — Modbus-RTU Method

4-4 Communication Function „ Register Number List R/W in the list shows whether the coil or holding register accepts reading and/or writing. R: Read only R/W: Read and write enabled 4 Functions *1. When either the control circuit terminal block or the coil is turned on, these settings are ON. The control circuit terminal block has the priority for the multi-function input terminals. If the master cannot reset the coil ON status because of communication disconnection, turn the control circuit terminal block from ON to OFF to turn off the coil. *2. The communications error is retained until a fault reset is input. (Can be reset during operation.) 4-165 Coil No.

Item R/W Description 0000h Not used  0001h RUN command R/W 1: Run 0: Stop (Enabled when A002 = 03) 0002h Rotation direction command R/W 1: Reverse 0: Forward (Enabled when A002 = 03) 0003h External trip (EXT) R/W 1: Trip 0004h Trip reset (RS) R/W 1: Reset 0005h Not used  0006h Not used  0007h Multi-function input terminal S1 R/W 1: ON 0: OFF *1 0008h Multi-function input terminal S2 R/W 1: ON 0: OFF *1 0009h Multi-function input terminal S3 R/W 1: ON 0: OFF *1 000Ah Multi-function input terminal S4 R/W 1: ON 0: OFF *1 000Bh Multi-function input terminal S5 R/W 1: ON 0: OFF *1 000Ch Multi-function input terminal S6 R/W 1: ON 0: OFF *1 000Dh Multi-function input terminal S7 R/W 1: ON 0:

OFF *1 000Eh Multi-function input terminal S8 R/W 1: ON 0: OFF *1 000Fh Operation status R 1: Run 0: Stop (Interlocked with d003) 0010h Rotation direction R 1: Reverse 0: Forward (Interlocked with d003) 0011h Inverter ready R 1: Ready 0: Not ready 0012h Not used  0013h RUN (during RUN) R 1: During trip 0: Normal