4-4 Communication Function 4 Functions 4-175 Register No. Function name Function code R/W Monitor and setting parameters Resolution 1103h Acceleration time 1 F002 (HIGH) R/W 1 to 360000 0.01 [s] 1104h F002 (LOW) 1105h Deceleration time 1 F003 (HIGH) R/W 1 to 360000 0.01 [s] 1106h F003 (LOW) 1107h Operator rotation direction selection F004 R/W 0: Forward 1: Reverse 1108h to 1200h Not used Register No. Function name Function code R/W Monitor and setting parameters Resolution 1201h Frequency reference selection A001 R/W 0: Digital Operator (FREQ adjuster) 1: Terminal 2: Digital Operator (F001) 3: ModBus communication 4: Option 1 5: Option 2 6: Pulse train frequency 7: Not used 10:
Frequency operation result 1202h RUN command selection A002 R/W 1: Terminal 2: Digital Operator (F001) 3: ModBus communication 4: Option 1 5: Option 2 1203h Base frequency A003 R/W 30 to Max. frequency 1 [Hz] 1204h Maximum frequency A004 R/W 30 to 400 1 [Hz] 1205h FV/FI selection A005 R/W 0: Switches between FV/FI 1: Switches between FV/FE 2: Switches between FV/VR 3: Switches between FI/VR 4: Switches between FE/VR 1206h FE selection A006 R/W 0: FE only 1: FV/FI auxiliary speed (not reversible) 2: FV/FI auxiliary speed (reversible) 3: FE disabled 1207h to 120Ah Not used