omron — Modbus-RTU Method

4-4 Communication Function 4 Functions 4-209 Register No. Function name Function code R/W Monitor and setting parameters Resolution 3103h 3rd acceleration time 1 F302 (HIGH) R/W 1 to 360000 0.01 [s] 3104h F302 (LOW) R/W 3105h 3rd deceleration time 1 F303 (HIGH) R/W 1 to 360000 0.01 [s] 3106h F303 (LOW) R/W 3107h to 3202h Not used    Register No. Function name Function code R/W Monitor and setting parameters Resolution 3203h 3rd base frequency A303 R/W 30 to 3rd max. frequency 1 [Hz] 3204h 3rd maximum frequency A304 R/W 30 to 400 1 [Hz] 3205h to 3215h Not used    3216h 3nrd multi-step speed reference 0 A320 (HIGH) R/W 0, Starting frequency to 3rd max.

frequency 0.01 [Hz] 3217h A320 (LOW) R/W 3218h to 323Bh Not used    323Ch 3rd manual torque boost voltage A342 R/W 0 to 200 0.1 [%] 323Dh 3rd manual torque boost frequency A343 R/W 0 to 500 0.1 [%] 323Eh 3rd V/f characteristics selection A344 R/W 0: VC 1: VP  323Fh to 326Ch Not used    326Dh 3rd acceleration time 2 A392 (HIGH) R/W 1 to 360000 0.01 [s] 326Eh A392 (LOW) R/W 326Fh 3rd deceleration time 2 A393 (HIGH) R/W 1 to 360000 0.01 [s] 3270h A393 (LOW) R/W 3271h to 330B Not used   