omron — Extended Function Mode

Appendix-1 Parameter List Appendix * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. App-5 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Set value Analog input, Others A005 FV/FI selection 00: Switches between FV/FI via terminal AT 01: Switches between FV/FE via terminal AT 02: Switches between FV/FREQ adjuster via terminal AT (Enabled only when 3G3AX-OP01 is used) 03: Switches between FI/FREQ adjuster via terminal AT (Enabled only when 3G3AX-OP01 is used) 04:

Switches between FE/FREQ adjuster via terminal AT (Enabled only when 3G3AX-OP01 is used) 00 No  A006 FE selection 00: FE only 01: FV/FI auxiliary frequency reference (not reversible) 02: FV/FI auxiliary frequency reference (reversible) 03: FE disabled 03 No  A011 FV start frequency 0.00 to 99.99 100.0 to 400.0 0.00 No Hz A012 FV end frequency 0.00 to 99.99 100.0 to 400.0 0.00 No Hz A013 FV start ratio 0. to FV end ratio 0. No % A014 FV end ratio FV start ratio to 100. 100. No % A015 FV start selection 00: External start frequency (A011 set value) 01: 0 Hz 01 No  A016 FV, FE, FI sampling 1. to 30. 31. (with 500 ms filter ± 0.1 Hz hysteresis) 31. No  A017 Not used Use "00".

* Do not change. 00 No 