omron — Extended Function Mode

3-7 Parameter List Extended Function Mode 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-22 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Basic setting A001 Frequency reference selection 00: Digital Operator (FREQ adjuster) (Enabled when 3G3AX-OP01 is used.) 01: Terminal 02: Digital Operator (F001) 03: ModBus communication 04: Option 1 05: Option 2 06: Pulse train frequency 07: Not used 10: Operation function result 02 No  4-10 4-134 A002 RUN command selection 01: Terminal 02: Digital Operator (F001) 03: ModBus communication 04: Option 1 05:

Option 2 02 No  4-11 A003 Base frequency 30. to Maximum frequency [A004] 60. No Hz 4-11 4-107 A203 * 2nd base frequency 30. to 2nd maximum frequency [A204] 60. 4-11 A303 * 3rd base frequency 30. to 3rd maximum frequency [A304] 60. A004 Maximum frequency 30. to 400. 60. No Hz 4-12 A204 * 2nd maximum frequency 30. to 400. 60. A304 * 3rd maximum frequency 30. to 400. 60.