3-7 Parameter List 3 Operation * 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001 to C008. 3-38 Parameter No. Function name Monitor or data range Default setting Changes during operation Unit Page Others b120 Brake control selection 00: Disabled 01:
Enabled 00 No 4-74 b121 Brake wait time for release 0.00 to 5.00 0.00 No s b122 Brake wait time for acceleration 0.00 to 5.00 0.00 No s b123 Brake wait time for stopping 0.00 to 5.00 0.00 No s b124 Brake wait time for confirmation 0.00 to 5.00 0.00 No s b125 Brake release frequency 0.00 to 99.99 100.0 to 400.0 0.00 No Hz b126 Brake release current 0.0 to 2.00 × Rated current Rated current No b127 Brake input frequency 0.00 to 99.99 100.0 to 400.0 0.00 No Hz b130 Overvoltage protection function selection during deceleration 00: Disabled 01: DC voltage kept constant 02: Acceleration enabled 00 No 4-75 b131 Overvoltage protection level during deceleration 200-V class:
330 to 390 400-V class: 660 to 780 380/ 760 No V b132 Overvoltage protection parameter 0.10 to 30.00 1.00 No s b133 Overvoltage protection proportional gain setting 0.00 to 2.55 0.50 Yes b134 Overvoltage protection integral time setting 0.000 to 9.999 10.000 to 65.53 0.060 Yes s