Danfoss — Руководство по эксплуатации Danfoss VLT 2900 (EN)

VLT ® 2900 Series Operation & Display 1. the [START] key. This cannot, however, override stop commands via the digital inputs (see parameter 013 Local control ). 2. the [STOP/RESET] and [JOG] keys, on the condition that these are active. English (english) [0] 3. the [FWD/REV] key, on the condition that is has been selected as active in parameter 016 Local reversing , and that parameter 013 Local control is set at Local control and open loop [1] or Local control as parameter 100 [3]. Pa- rameter 200 Output frequency range is set at Both directions .

German (deutsch) [1] French (francais) [2] Danish (dansk) [3] Spanish (espanol) [4] Italian (italiano) [5] This parameter is used to choose the language to be shown in the display whenever the LCP control unit is connected. 4. parameter 003 Local reference where the ref- erence can be set using the [+] and [-] keys. 5. an external control command that can be connected to the digital inputs (see parame- ter 013 Local control ). There is a choice of the languages shown. The factory setting may vary. NB! The [JOG] and [FWD/REV] keys are lo- cated on the LCP control unit. Programming Remote operation (REMOTE) [0] Local operation (LOCAL) [1] Par. 013 Local control must be set to [1] or [2]:

0 - f MAX (par. 202) There is a choice of two different modes of operation of the frequency converter; Remote operation [0] or Local operation [1]. See also parameter 013 Local con- trol if Local operation [1] is selected. 50 Hz Par. 013 Local control must be set to [3] or [4]. Ref MIN - Ref MAX (par. 204-205) In this parameter, the local reference can be set man- ually. The unit of the local reference depends on the configuration selected in parameter 100 Configuration . 0,0 If Remote operation [0] is selected, the frequency con- verter is controlled via: 1. the control terminals or via serial communi- cation.

In order to protect the local reference, parameter 002 Local/remote operation must be set to Local op- eration [1]. Local reference cannot be set via serial communication. 2. the [START] key. This cannot, however, override stop commands transmitted via the digital inputs or via serial communication. 3. the [STOP/RESET] and [JOG] keys, on the condition that these are active. If Local operation [1], is selected, the frequency con- verter is controlled via: = factory setting, () = display text, [] = value for use in communication via serial communication port MG.29.A3.02 - VLT ® is a registered Danfoss trademark 11 001 Language (language) Value: Function: Description of choice:

002 Local/remote operation (OPERATION SITE) Value: 003 Local reference (LOCAL REFERENCE) Value: Function: Function: Description of choice: Description of choice: