VLT ® 2900 Series Parameter 007 LCP copy is used if you want to use the LCP 2 control panel's integral copy function. The func- tion is used if you want to copy all parameter setups from one frequency converter to another by moving the LCP 2 control panel. Frequency [Hz] (Frequency [Hz]) [4] Output frequency x scaling (frequency x scale) [5] Motor current [A] (Motor current [A]) [6] Torque [%] (Torque [%]) [7] Power [kW] (Power [kW]) [8] Select Upload all parameters [1] if you want all param- eter values to be transferred to the control panel.
Se- lect Download all parameters [2] if all parameter values transferred are to be copied to the frequency converter to which the control panel is attached. Select Down- load size-independent par. [3] if you only want to down- loade the size-independent parameters. This is used when downloading to a frequency converter with a dif- ferent rated power size than that from which the pa- rameter setup originates. Power [HP] (Power [HP][US]) [9] Motor voltage [V] (Motor voltage [V]) [11] DC link voltage [V] (DC link voltage [V]) [12] Thermal load motor [%] (Motor thermal [%]) [13] Thermal load [%] (FC. thermal[%]) [14] Running hours [Hours] (RUNNING HOURS]) [15] NB!
Upload/download can only be performed in stop mode. Download can only be per- formed to a frequency converter with the same software version number, see pa- rameter 626 Database identification no. Digital input [Bin] (Digital input[bin]) [16] Analog input 53 [V] (analog input 53 [V]) [17] Analog input 60 [mA] (analog input 60 [mA]) [19] Programming Pulse reference [Hz] (Pulse ref. [Hz]) [20] External reference [%] (external ref. [%]) [21] 0.01 - 100.00 Status word [Hex] (Status word [hex]) [22] 1.00 Heatsink temperature [°C] (Heatsink temp [°C]) [25] In this parameter, the factor is selected by which the output frequency is to be multiplied.
The value is shown in the display, provided parameters 009-012 Display readout have been set to Output frequency x scaling [5]. Alarm word [Hex] (Alarm word [hex]) [26] Control word [Hex] (Control word [Hex]) [27] Warning word [Hex] (warning word [Hex]) [28] Extended status word [Hex] (Ext. status [hex]) [29] Set the required scaling factor. Communication option card warning (COMM OPT WARN [HEX]) [30] Pulse count (PULSE COUNTER) [31] In this parameter you can select the data value that you wish to display in the LCP 2 control unit display line 2 when the frequency converter is switched on. The display will also be included in the scrollbar in dis- play mode.
In parameters 010-012 Display readout you No readout (none) [0] Resulting reference [%] (reference [%]) [1] Resulting reference [unit] (reference [unit]) [2] Feedback [unit] (feedback [unit]) [3] = factory setting, () = display text, [] = value for use in communication via serial communication port MG.29.A3.02 - VLT ® is a registered Danfoss trademark 13 Function: Description of choice: 008 Display scaling of output frequency (FREQUENCY SCALE) Value: Function: Description of choice: 009 Large display readout (DISPLAY LINE 2) Value: Function: