*1 Refer to user’s manual for full set value Example of Parameter Settings Note 1: To cancel the set value, press the Mode Key instead, The parameter number will be displayed. 2: There are parameters that cannot be changed while the Inverter is in operation. Refer to the list of parameters. When attempting to change such parameters, the data display will not change by pressing the Increment or Decrement Key.
Multi-function Inputs Multi-function Outputs Value*1 Function Value*1 Function 8 Multi-step speed reference 3 15 Undervoltage in progress 10 Inching Command Analogue Output Functionsts 12 External base block (NO) Value*1 Function 13 External Base block (NC) 0 Otput frequency 17 Local/Remote selection 1 Output current Cancels Set Data In approximately 1s. Key Sequence Indicator Display example Explanation Power On Press the Mode Key repeatedly until the PRGM indicator is lit. Use the Increment or Decrement Key to set the parameter number. Press the Enter Key. The data of the selected parameter number will be displayed. Use the Increment or Decrement Key to set the data.
At that time, the display will flash. Press the Enter Key so that the set value will be entered and the data display will be lit (see note 1) In approximately 1s. The parameter number will be displayed.