omron · 12 стр.

Y203-EN2-05+MotionDrives+Cat (EN)

Оригинальное название: Y203-EN2-05+MotionDrives+Cat

Читать онлайн

Похожие инструкции

Текст документа

Frequency inverters System configuration Power Supply Panel Kit ~ I/O option board SX-D Communication Option Board Feedback Speed Option Card ~ PTC/PT100 Option Card Output Coils Brake resistor Motor Overshoot clamp Ground 249 SX (400V) SX (400V) High performance Vector Control • IP54 full range.

• Compact design & Robustness • Built-in Filter according to C3 Class • Built-in Fusses (From 200 kW) • Safety according EN13849-1 and EN62061 standards • Load curve control • HCB technology (Half controlling Bridge) • Logic programmability • Pre-maintenance alarms • Options flexibitity (I/O’s, Fieldbus, PTC/PT100, Multiple Pump control, Encoder, Crane control) • Communications options (Modbus, Dnet, Profibus) • 24 VDC control board supply • Liquid cooling drive version • 12-pulse rectifier option. • Flexible cable connections & User Friendly wiring connection • CE, UL, RoHS, DNV Ratings • 400 V Class three-phase 0.75 to 800 kW

Стр. 1

Specifications Type designation S X - D 4 1 6 0 - E F - O P T I O N S sx series Check below table Protection Class: D: IP54 A: IP20 Voltage: 4: 400 / 480 VAC 6: 690 VAC Control type: V: V/Hz F: Direct Torque Control Rated Power: 0P7: 0.75 kW ~ 800: 800 kW Market: E: Europe Options available 400 V class 1.

Based on a standard 4-pole motor for maximum applicable motor output 400 V class 250 Frequency inverters Options Letter (“?” means no character) Options Letter (“?” means no character) Control panel “?” = Standard control panel (Std.PPU) “A”= Blank control panel (Blank PPU) Option board position 3 “?” = No option “I” = Encoder “J” = PTC/PT100 “K” = Extended I/O“ Built-in EMC filter “?” = Standard EMC inside (Category C3) “B” = IT-Net (filter disconnected from ground) Option board Fieldbus position 4 “?” = No option “L” = DeviceNet “M” = Profibus-DP “N” = RS232/485 “O” = EtherNet Modbus TCP Built-in brake chopper “?” = No brake chopper or DC-connection included “C” = Brake chopper & DC-connection included “D” = Only DC-connection included Liquid Cooling “?” = No Liquid Cooling “P” = Liquid Cooling Standby power supply “?” = Not included “E” = Standby power supply included Standard “?” = IEC “Q” = UL Safe stop “?” = Not included “F” = Safe stop included Marine “?” = No marine option “R” = Marine option included Coated boards “?” = No coating “G” = Coated boards Cabinet input options “?” = No cabinet input options “S” = Main switch included “T” = Main contactor included “U” = Main switch + contactor included Option board position 1 “?” = No option “H” = Crane I/O “I” = Encoder “J” = PTC/PT100 “K” = Extended I/O“ Cabinet output options “?” = No cabinet output options included “V” = dV/dt filter included “W” = dV/dt filter + Overshoot clamp included “X” = Sinusfilter included Option board position 2 “?” = No option “I” = Encoder “J” = PTC/PT100 “K” = Extended I/O“ additional options “Z1” = Common mode output filter “Z2” = Cable gland kit “Z3” = Motor PTC connection Only models from 0.37 to 37KW Three-phase:

SX-@4@@@-E@ 0P7 1P5 2P2 3P0 4P0 5P5 7P5 011 015 018 022 030 037 045 055 Motor kW1 For HD setting 0.55 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 For ND setting 0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 Output characteristics Max output current (A) @-EF 3.8 6.0 9.0 11.3 14.3 19.5 27.0 39.0 46.0 55.0 69.0 92.0 111 108 131 Max output current (A) @-EV 3.0 4.8 7.2 9.0 11.4 15.6 21.6 31.0 37.0 44.0 55.0 73.0 89.0 108 131 Rated output current (A) at HD 2.0 3.2 4.8 6.0 7.6 10.4 14.4 21.0 25.0 29.6 37.0 49.0 59.0 72.0 87.0 Rated output current (A) at ND 2.5 4.0 6.0 7.5 9.5 13.0 18.0 26.0 31.0 37.0 46.0 61.0 74.0 90.0 109 Output voltage 0 to Mains supply voltage Max.

output frequency 400 Hz Power supply Rated input voltage and frequency 3-phase 230..480 V 50/60 Hz Allowable voltage fluctuation +10%..-15% (-10% at 230V) Allowable frequency fluctuation 45 to 65 Hz Three-phase:

SX-@4@@@-E@ 075 090 110 132 160 200 220 250 315 355 400 450 500 630 800 Motor kW For HD setting 55 75 90 110 132 160 200 220 250 315 355 400 450 500 630 For ND setting 75 90 110 132 160 200 220 250 315 355 400 450 500 630 800 Output characteristics Max output current (A) @-EF 175 210 252 300 360 450 516 600 720 780 900 1032 1200 1440 1800 Max output current (A) @-EV 175 210 252 300 360 450 516 600 720 780 900 1032 1200 1440 1800 Rated output current (A) at HD 117 140 168 200 240 300 344 400 480 520 600 688 800 960 1200 Rated output current (A) at ND 146 175 210 250 300 375 430 500 600 650 750 860 1000 1200 1500 Output voltage 0 to Mains supply voltage Max.

output frequency 400 Hz Power supply Rated input voltage and frequency 3-phase 230..480 V 50/60 Hz Allowable voltage fluctuation +10%..-15% (-10% at 230V) Allowable frequency fluctuation 45 to 65 Hz

Стр. 2

Specifications Common specifications Frequency inverters SX (400V) 251 Model number SX- Specifications Control functions Control methods V/f control for “V” type V/f control, Vector control with or without feedback for the “F” type Output frequency range 0.0..400 Hz Frequency tolerance Analogue set value: 1% + 1.5 LSB fsd Resolution of frequency set value Digital set value: 0.1 Hz Analogue set value:

0.03 Hz / 60 Hz (11 bit + sign) Resolution of output frequency 0.1 Hz Frequency set value -10..+10 V (20 k), 0..20 mA (250 ), frequency setting value (selectable) Starting Torque 150% for Heavy duty, 120% for Normal duty Torque static accuracy Torque response 1 ms for 0 - 90% speed 5 ms for 90 - 100% speed (Close and open loop) Speed Control Accuracy V/f control 1% Vector control without feedback 0.1% Vector control with feedback 0.01% Speed Response 0.4% without encoder feedback 0.2% with encoder feedback Torque Limit From Analog input Accel/Decel Time 0.0 to 3600.0 s Braking torque 5 - 10% (100% with external braking resistor) Functionality Main Control Functions PID, sleep function, brake control, torque control (Direct torque control model), Pump/Fan control, Logic functions, virtual connections, overvoltage control, undervoltage override, autoreset, two motor support, Lim Switch, External trip, Preset Speeds, MotPot Up Down, Pump Feedback, Timer, Mot PreMag , Jog, Ext Mot Temp, Loc/Rem, AnIn select, Brk Ackn.

Protection functions Motor protection Motor overheat protection based on output current or PTC by option board Momentary overcurrent Protection Drive stops when ouput current exceeds 200% of peak current Overload Protection Drive stops after 1 min at 150% of rated output current (Heavy Duty Rating) Drive stops after 1 min at 120% of rated output current (Normal Duty Rating) (1min every 10min) Overvoltage Protection Line Overvoltage: 760 VDC during more than 10s for 400 V class; Fast Overvoltage:

850 VDC for 400 V class Undervoltage Protection 400 VDC for 400 V class (Adjustable by input power supply parameter) Momentary power loss Ride-Thru Low voltage override function Heatsink Overheat Protection Protected by thermister Braking Resistance Overheat Protection Hardware short circuit protection Stall prevention Current limit function Power charge indication Power LED remains lit until capacitors are charged Ambient conditions Ambient Temperature 0ºC..+40ºC, up to 45ºC with derating Ambient humidity 90% RH or less (without condensation) Storage temperature -20ºC..+60ºC (short-term temperature during transportation) Altitude Up to 1000 meters (output derating of 1% per 100 m above 1000 m, max.

2000 m) Vibration / Shock According to IEC 600068-2-6, Sinusodial vibrations: 10 Contamination, according to IEC 60721-3-3 No electrically conductive dust allowed. Cooling air must be clean and free from corrosive materials. Chemical gases, class 3C2. Solid particles, class 3S2 Protection Design IP54 enclosure according to the EN 60529

Стр. 3

Dimensions Standard dimensions IP54 SX-D4011 to D4022 SX-D4030 to D4037 SX-D40P7 to D47P5 351 32.5 36,4 30 545 416 512 590 191 200 202.6 210 292,1 220 295 SX-D4045 to D4090 SX-D4110 to D4132 Ш9(x6) 22,50 120 240 Ш9(6x) 284,50 275 10 925 300 22.50 150 30 920 335 344,5 10 Ш16(3)x) 30 920 Ш16(3x) 925 950 950 314 314 252 Frequency inverters 439,2 172 178

Стр. 4