Delta — Delta Electronics — инструкция

Ethernet Communication Module IFD9506 1. Use DVPACAB2A30 cable to connect the PC and IFD9506. Open the setup page. 2. Check “Factory Setting” box and the warning dialog box will appear. Click on “Yes” to return to default settings (in approx. 5 ~ 10 seconds), and the password will be cleared as well. 10.3 IP Filter Protection 1. See 8.1 for the connection and how to set up the communication. 2. Open the setup page and switch to “IP Filter” page. 3. Check “ Enable IP Filter” box. Enter “192.168.0.7” into No. 1 IP and “255.255.255.255” in all “Netmask” columns. DVP-PLC Application Manual 40 Application Setting up IP filter protection.

Only connections to 192.168.0.7 and 172.16.0.1 ~ 172.16.0.255 are allowed. Steps (1) Check "Enable IP Filter” box. (2) Set up IP address to “192.168.0.7” and netmask to “255.255.255.255”. (3) Set up IP addres to “172.16.0.1” and netmask to “255.255.255.0”.