P393 Linearizer, Point 2 Enter the load, in units of P017, for point 2. P394 Compensation, Point 2 Enter the calculated compensation, in percent, for compensation point 2. P395 Linearizer, Point 3 Enter the load, in units of P017, for point 3. P396 Compensation, Point 3 Enter the calculated compensation, in percent, for compensation point 3. End of Linearization Parameters. Totalization (P619 - P648) Parameters The following parameters are specific to the use to the BW100 totalizers. Refer also to Operation/Totalization, page 45. Note: If the resolution (P631 - P639) selected would cause the totalizer to lag behind the count rate, a message E2 is displayed after making the entry.
Select a greater resolution value. Example Given: P005 = 1 (t/h) P631 = 5 Then: totalizer count increments by 10 for each 10 metric tonne registered P619 Totalizer Drop Out This parameter sets the limit, in percent of design rate, below which material rates are not totalized. The value of 0 is reserved to allow both negative and positive totalization. Enter drop out value in % of design rate. Page 58 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01