Lenze — 6.2 General data and operating conditions

DC power supply modules General data and operating conditions 6 6.2 Mounting conditions Mounting place Mounting position Mounting clearances Above/below Observe the device-related notes on mounting. To the sides Supply systems Operating conditions Environmental conditions Climate Vibration resistance (9.81 m/s 2 = 1 g)  6.2-2 EDS94SPP101 EN 3.1-04/2007 Vertical ≥80 mm / ≥120 mm Side-by-side mounting without any clearance Connection conditions for DC power supply module AC mains operation Direct connection DC-bus operation Direct connection of axis modules via terminals or busbar system More information can be found in the Hardware Manual, chapter ”DC-bus operation”.

TT TN With earthed phase IT Operation permitted without restrictions. Operation permitted if additional measures are taken: z The protection of persons according to EN 61800-5-1 requires the supplementary insulation of control cables. z The measures described for IT systems have to be taken. Operation permitted without restrictions. Storage Transport Operation IEC/EN 60721-3-1 1K3 (-25 ... +60 °C) IEC/EN 60721-3-2 2K3 (-25 ... +70 °C) IEC/EN 60721-3-3 3K3 (-10 ... +55 °C) Current derating at +45 ... +55 °C: 2.5 %/°C Site altitude 0 ... 4000 m amsl 1000 ... 4000 m amsl:

current derating of 5 %/1000 m Pollution EN 61800-5-1 Pollution degree 2 Transport Operation IEC/EN 60721-3-2 2M2 EN 61800-2 2 ... 9 Hz: amplitude 3.5 mm 10 ... 200 Hz: acceleration resistant up to 10 m/s2 200 ... 500 Hz: acceleration resistant up to 15 m/s2 Germanischer Lloyd 5 ... 13.2 Hz: amplitude ±1 mm 13.2 ... 100 Hz: acceleration resistant up to 0.7 g EN 50178 10 ... 57 Hz: amplitude 0.075 mm 57 ... 150 Hz: acceleration resistant up to 10 m/s2