Lenze — 6.3.3 Operation at rated mains voltage 500 V

DC power supply modules Rated data (devices for 400/500V mains) Operation at rated mains voltage 500 V 6 6.3 6.3.3 Output data c Temperature in the control cabinet 100 % Permanent rated values Cycle 1 Cycle for the second-range (0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value) Cycle 2 Cycle for the minute-range (60 s overload/120 s recovery time with 75 % of the permanent rated value)  6.3-9 EDS94SPP101 EN 3.1-04/2007 Basis of the data Mains Rated voltage UDC [V] Voltage range UDC [V] Frequency range [Hz] 705 565 - 0 % ... 775 + 0 % Voltage Frequency Current [A] Number of phases Type [V] [Hz] max. +45 °C c max.

+55 °C c 705 0 (DC) 10 7.5 705 0 (DC) 36 27 705 0 (DC) 100 75 705 0 (DC) 245 184 Output current and output power 100 % Cycle 1 Cycle 2 Type IDC [A] PDC [kW] IDC [A] PDC [kW] IDC [A] PDC [kW] E94APNE0104 10 4.5 40 18.0 15 6.8 E94APNE0104 + E94AZMP0084 10 6.1 40 24.4 15 9.2 E94APNE0364 36 16.3 108 48.9 54 24.5 E94APNE0364 + E94AZMP0294 36 21.9 108 65.7 54 32.9 E94APNE1004 100 45.2 200 136 150 67.8 E94APNE100 + E94AZMP0824 100 60.8 200 182 150 91.2 E94APNE2454 245 111 368 333 368 167 E94APNE2454 + E94AZMP2004 245 149 368 447 368 224