Lenze — 7.4.1 General data

DC-bus operation Rated data General data 7 7.4 7.4.1 7.4 Rated data 7.4.1 General data For dimensioning the DC cables, you must know the input current. The number of devices in a drive system can be limited by the DC-bus capacity and the charging current. Multi Drives Single Drives Tab. 7.4-1 1) Devices may not be used as direct DC bus devices on the DC-bus level because the charging current is not limited.

 7.4-1 EDS94SPP101 EN 3.1-04/2007 Additional data Type Input current DC-bus capacity Charging resistor IDC with IaN8 [A] [μF] [Ω] E94AMxE0024 2.6 165 200 E94AMxE0034 4.3 165 200 E94AMxE0044 6.7 330 200 E94AMxE0074 12.1 330 200 E94AMxE0094 15.4 495 200 E94AMxE0134 20.6 495 100 E94AMxE0174 25.7 825 100 E94AMxE0244 35.5 990 100 E94ASxE0024 2.6 165 400 E94ASxE0034 4.3 165 400 E94ASxE0044 6.7 330 200 E94ASxE0074 12.1 330 200 E94ASxE0134 20.6 495 100 E94ASxE0174 25.7 825 100 E94ASxE0244 35.5 990 100 E94ASxE0324 35.5 2200 68 E94ASxE0474 45.9 2200 68 E94ASxE0594 45.9 2200 68 E94ASxE0864 1) 82.2 3300 68 E94ASxE1044 1) 87.3 3300 68 E94ASxE1454 1) 120 7050 32 E94ASxE1724 1) 142 7050 32 E94ASxE2024 1) 156 7050 32 E94ASxE2454 1) 190 7050 32 E94ASxE2924 1) 223 9040 32 E94ASxE3664 1) 282 11750 32