Lenze — 7.4.4 DC fuses

7 7.4 7.4.4 DC-bus operation Rated data DC fuses 7.4.4 DC fuses Fuse the individual +UG/-UG cables to protect the DC-bus connection. The DC-bus connection is protected against damage through a DC earth fault or short circuit in a device. Multi Drives Single Drives Tab. 7.4-6 z K = indicator, N = no indicator If fuses have tripped in case of an error, fuses connected upstream of other devices may have been damaged before. If so, we recommend to replace them.  Warnings! For installation to UL, select approved fuses with the same tripping characteristic and a suitable voltage class.

 7.4-6 EDS94SPP101 EN 3.1-04/2007 Controller/DC fuse assignment Type Rated value Type Size Number per [A] (SIBA) [mm] or size +UG/-UG E94AMxE0024 E94AMxE0034 E94AMxE0044 16 EFSGR0160AYHz 14 x 51 1 EFSGR0160AYIz 22 x 58 E94AMxE0074 E94AMxE0094 32 EFSGR0320AYHz 14 x 51 EFSGR0320AYIz 22 x 58 E94AMxE0134 E94AMxE0174 E94AMxE0244 63 EFSGR0630AYIz 22 x 58 E94ASxE0024 E94ASxE0034 16 EFSGR0160AYHz 14 x 51 1 EFSGR0160AYIz 22 x 58 E94ASxE0044 E94ASxE0074 32 EFSGR0320AYHz 14 x 51 EFSGR0320AYIz 22 x 58 E94ASxE0134 E94ASxE0174 E94ASxE0244 63 EFSGR0630AYIz 22 x 58 E94ASxE0324 E94ASxE0474 E94ASxE0594 100 EFSGR1000AYIz 22 x 58 EFSGR1000ANVz NH1 E94ASxE0864 E94ASxE1044 200 EFSGR2000ANVz NH1 E94ASxE1454 250 EFSGR2500ANWz NH2 E94ASxE1724 E94ASxE2024 350 EFSGR3500ANWz NH2 E94ASxE2454 E94ASxE2924 500 EFSGR5000ANWz NH2 E94ASxE3664 350 EFSGR3500ANWz NH2 2 (in parallel) E94ASxE4604 350 EFSGR3500ANWz NH2 3 (in parallel) E94ASxE5724 350 EFSGR3500ANWz NH2 E94ASxE6354 400 EFSGR4000ANWz NH2 E94ASxE6954 400 EFSGR4000ANWz NH2