Lenze — 4.4.3 Devices in the range 145 695 A ( 75 400 kW)

Single-axis controllers Device description Devices in the range 145 ... 695 A (75 ... 400 kW) 4 4.4 4.4.3 The LED display enables fast indication of several operating states.  4.4-7 EDS94SPP101 EN 3.1-04/2007 Design Pos. Description HighLine StateLine MXI1 Module receptacle for extension 1, e.g. communication ; ; MXI2 Module receptacle for extension 2, e.g.

communication ; † MMI Module receptacle for memory modules ; ; MSI Module receptacle for safety equipment ; ; X1 System bus (CAN), under the cover ; † X2 24-V supply / Statebus ; ; X3 Analog inputs / analog outputs 2/2 1/0 X4 Digital outputs 4 1 X5 Digital inputs 8 4 X6 Diagnostics (with diagnostic adapter or keypad) ; ; X7 Resolver ; ; X8 Encoder ; ;  Lower cap ; ;  Nameplate, retractable ; ;  Upper cap ; ;  EMC wire clamp Optional X100 Mains / DC-bus voltage ; ; X105 Motor / external brake resistor ; ; X106 Motor temperature monitoring (position depends on the device size) ; ; X107 Control of motor holding brake Optional  EMC shield clamp 2 2  Holes for transport and assembly guides 4 4  Shield connection/strain relief (device sizes:

8S, 8 and 9) ; ;  Barrier between mains input and other power terminals (device sizes: 8S, 8 and 9) ; ;  Switch for operation in IT systems ; ; LED Labelling Colour Description SSP94LED01 CAN-RUN green CAN bus o.k. CAN-ERR DRIVE READY red green DRIVE ERROR red Error in the standard device or due to the application 24 V green 24-V supply voltage o.k. USER yellow Message parameterised by the application Pos. Symbol Description   Long discharge time: All power terminals carry hazardous voltages for at least 20 minutes after mains disconnection!  High discharge current: Fixed installation and PE connection to EN 61800-5-1 required!  Electrostatic sensitive devices:

Before working on the device, the personnel must remove any electrostatic charges using suitable measures!