4 4.6 4.6.3 Single-axis controllers Wiring Devices in the range 2 ... 24 A (0.37 ... 11 kW) a b U V W M5 PE BD1/T1 BD2/T2 c d e SSP94MOTL1 Fig.
4.6-3 Stripping lengths of the motor cable How to proceed: 1. Strip the motor cable according to dimensions given. 2. Fold back the shield of the motor cable over the cable sheath. 3. Stabilise the shield with self-adhesive conductive foil (recommendation). 4. Fix the shield and conductive foil with heat-shrinkable tube on the cable sheath. 5. Fasten cable lugs or wire end ferrules. 6. Connect the shields separately to the shield sheet using shield clamps (no strain relief). E94AZPS004 4.6-12 EDS94SPP101 EN 3.1-04/2007 Dimensions [mm] Type a b c d e Device size 1 80 8 25 150 8 Device size 2 90 8 30 160 8 Device size 3 100 1 0 30 170 8