sinee — 9.2 Function Parameter List

A90 series Inverter User Guide Table 9-4 Analog Output Terminal Functions 50 Set value function Set function value 0 Running Frequency (absolute value) 15 Length Value 1 Set Frequency (absolute value) 16 The PID Output Percentage 2 Output torque (absolute value) 18 PID Feedback 3 Set Torque (absolute value) 19 PID Given 4 Output Current 21 Output frequency (actual value) 5 Output Voltage 22 Set frequency (actual value) 6 DC Bus voltage 23 Output current (actual value) 7 Output power 24 Output torque (actual value) 8 AI1 25 Set torque (actual value) 9 AI2 27 Estimated feedback frequency (actual value) 13 Communication given 28 Synchronous frequency (actual value) 14 The Count Value 29 Acceleration / deceleration output frequency (actual value) F04 Start/Stop Control Parameter Group F04.00 Start Mode 0:

Start Directly 1: Speed Tracking Start 0 〇 F04.01 Start Frequency 0.00 - 10.00 Hz 0.00 〇 F04.02 Start Frequency Retention Time 0.00 - 60.00, Disabled at 0.00 s 0.00 〇 F04.03 DC Brake Current at Start 0.0 - 100.0 (100.0= Motor Rated Frequency) % 100.0 〇 F04.04 DC Brake Time at Start 0.00 - 30.00 s 0.00 〇 F04.06 Pre-Excitation Current 50.0 - 500.0 (100.0=Idling Current) % 100.0 〇 F04.07 Pre-Excitation Time 0.00 - 10.00 s 0.10 〇 F04.08 Speed Tracking Method Ones Place: the starting frequency 0: Start from Maximum Frequency 1: Start from Stop Frequency 2: Start from Power frequency Tens Place:search direction 0: Search only in command direction 1:

current direction can not find the speed then search the reverse direction 01 〇 F04.10 Deceleration Time of Speed Tracking 0.1~20.0 s 2.0 〇 F04.11 Speed Tracking Current 30.0~150.0 (100.0=Inverter Rated Current) % 50.0 〇 F04.12 Speed Tracking Compensation Gain 0.00~10.00 1.00 〇