A90 series Inverter User Guide 64 F16.13 Set Resolution Of The Length 0:1m 1:0.1m 2:0.01m 3:0.001m 0 〇 F17 Virtual I/O Function Group This group of parameters users generally do not need to adjust, please refer to A90 user guide or visit www.sineedrive.com download function table electronic version.
F18 Monitoring Parameter Group F18.00 Output Frequency 0.00 - Upper Limit Frequency Hz XXX × F18.01 Set Frequency 0.00 - Maximum Frequency F00.16 Hz XXX × F18.03 Estimated Feedback Frequency 0.00 - Upper Limit Frequency Hz XXX × F18.04 Output Torque -200.0 - 200.0 % XXX × F18.05 Torque Setting -200.0 - 200.0 % XXX × F18.06 Output Current A XXX × F18.07 Output Current Percentage 0.0 - 300.0 (100.0= Inverter Rated Current) % 0.0 × F18.08 Output Voltage 0.0 - 690.0 V XXX × F18.09 DC bus Voltage 0 - 1200 V XXX × F18.10 Simple PLC Running Times 0 - 10000 XXX × F18.11 Simple PLC Running Stage 1 - 15 XXX × F18.12 PLC Running Time of Present Stage 0.0 - 6000.0 XXX × F18.14 Load Speed 0 - 65535 rpm XXX × F18.15 UP/DOWN Offset Frequency 0.00 - 2*Maximum Frequency F00.16 Hz XXX × F18.16 PID Setting 0.0 – PID Maximum Range XXX × F18.17 PID Feedback 0.0 – PID Maximum Range XXX × F18.18 Kilowatt-Hour Meter, MWh 0 - 65535 MW h XXX × F18.19 Kilowatt-Hour Meter, KWh 0.0 - 999.9 kWh XXX × F18.20 Output Power 0.00 - 650.00 kW XXX × F18.21 Output Power Factor -1.000 - 1.000 XXX × F18.22 Digital Input Terminal Status 1 X5 X4 X3 X2 X1 XXX × 0/1 0/1 0/1 0/1 0/1 F18.23 Digital Input Terminal Status 2 * AI2 AI1 * X6 XXX × * 0/1 0/1 * 0/1 F18.25 Output Terminal Status * * R1 * Y1 XXX × * * 0/1 * 0/1 F18.26 AI1 0.0~100.0 % XXX × F18.27 AI2 0.0~100.0 % XXX × F18.33 Count Value 0~65535 XXX ×