A90 series Inverter User Guide 10.3.3 The corresponding wiring diagram of the pump application macro power supply pressure Transmitter Ground External fault RUN/STOP Sleep indicator Fault output The paremeter list of Pump application macro F16.00=3:Pump application, restore the factory value, the parameters are as follows: Function: the process PID, continuious woking under instantaneous power failure, fault retry, sleep and wake up, pipe network overpressure alarm function Water pressure conversion relationship:
1bar= 0.1Mpa= 100kPa≈ 1kg/cm 2 70 24V Auxiliary power:24VDC,≤100mA AI2 Analog input:0-10V or 4-20mA GND Analog common COM Digital common X1 Digital input terminal X2 Digital input terminal X6 Digital input terminal COM Digital common terminal Y1 Digital output terminal EC Relay output EB EA A+ RS485 Communication port A- No. Function range Unit Default 0: Keypad Control F00.02 Command Source Options 1: Terminal Control 0 2: Communication Control Auxiliary Frequency F00.05 10: Process PID 10 Source B Options F00.06 Frequency Source Options 1:
Auxiliary Frequency Source B 1 F00.14 Acceleration Time 1 s 25.00 F00.15 Deceleration Time 1 s 30.00 F00.16 Maximum Frequency Hz 50.00 F00.18 Upper Limit Frequency Hz 50.00 Lower Limit Frequency F00.19 Hz 5.00 (Sleep frequency) F00.21 Reverse Control 1: Prohibit Reverse 1 F00.30 Load Type 1: Nomal duty 1 F02.00 X1 Digital Input Function 1: Run Terminal “RUN” 1 23: External Fault Input F02.01 X2 Digital Input Function With the external water shortage 23 signal terminal