sinee — The paremeter list of Fan application macro

A90 series Inverter User Guide 10.3.4 The corresponding wiring diagram of the fan application macro Frequency reference frequency output RUN/STOP Coast to stop Manual/Auto Fault reset Inverter running Fault output Communication port The paremeter list of Fan application macro F16.00=4:Fan application, After restoring the factory values, the parameters are shown in the following table: Function: with guide / automatic switching function, speed tracking start, continuious woking under instantaneous power failure, general failure retry function. Guide: F0.07 set the operating frequency, the keypad control start and stop; automatic: AI1 voltage given frequency, terminal control start and stop.

72 10V Analog terminal power:≤10mA AI1 Analog input:0-10V GND Analog common M1 Analog output:0-10V ≤2mA 24V Auxiliary power:24VDC,≤100mA X1 Digital input terminal X2 Digital input terminal X3 Digital input terminal X6 Digital input terminal COM Digital common terminal Y1 Digital output terminal EC Relay output EB EA A+ RS485 communication port A- No. Function Range Unit Default 0: Keypad Control Command Source Options F00.02 1: Terminal Control 1 (Automatic mode) 2:

Communication Control Main Frequency Source A F00.04 1:AI1(Automatic mode) 1 Options Digital Frequency F00.07 Manual mode frequency Hz 35.00 reference F00.14 Acceleration Time 1 s 25.00 F00.15 Deceleration Time 1 s 30.00 F00.16 Maximum Frequency Hz 50.00 F00.18 Upper Limit Frequency Hz 50.00 F00.19 Lower Limit Frequency Hz 0.00