User Manual of A90 Series Inverter 106 and 2 F15.13 Acceleration and deceleration time unit 0:0.01s 1:0.1s 2:1s 0 ○ F15.14 Frequency hopping point 1 0.00-600.00 Hz 600.00 ● F15.15 Hopping range 1 0.00-20.00, 0.00 is invalid Hz 0.00 ● F15.16 Frequency hopping point 2 0.00-600.00 Hz 600.00 ● F15.17 Hopping range 2 0.00-20.00, 0.00 is invalid Hz 0.00 ● F15.18 Frequency hopping point 3 0.00-600.00 Hz 600.00 ● F15.19 Hopping range 3 0.00-20.00, 0.00 is invalid Hz 0.00 ● F15.20 Detection width of output frequency arrival (FAR) 0.00 - 50.00 Hz 2.50 ○ F15.21 Output frequency detection FDT1 0.00 to maximum frequency F00.16 Hz 30.00 ○ F15.22 FDT1 hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 ○ F15.23 Output frequency detection FDT2 0.00 to maximum frequency F00.16 Hz 20.00 ○ F15.24 FDT2 hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 ○ F15.25 Options of analog level detection ADT 0:AI1 1:

AI2 0 ○ F15.26 Analog level detection ADT1 0.00-100.00 % 20.00 ● F15.27 ADT1 hysteresis 0.00 to F15.26 (valid down in one direction) % 5.00 ● F15.28 Analog level detection ADT2 0.00-100.00 % 50.00 ● F15.29 ADT2 hysteresis 0.00 to F15.28 (valid down in one direction) % 5.00 ● F15.30 Options of energy consumption braking function 0: Invalid 1: valid 0 ○ F15.31 Energy consumption braking voltage 110.0-140.0 (380V, 100.0 = 537V) % 125.0 (671V) ○ F15.32 Braking rate 20-100 (100 means that duty ratio is 1) % 100 ● F15.33 Operating mode with set frequency less than lower frequency limit 0: running at the lower frequency limit 1: Shutdown 2: zero-speed running 0 ○