User Manual of A90 Series Inverter ★ Correct selection of the inverter: The rated output current of the inverter is greater than or equal to the rated current of the motor, taking into account the overload capacity. ★ The difference between the rated power of the inverter and that of the motor is usually recommended not to exceed two power segments. ★ When a high-power inverter is provided with a low-power motor, the motor parameters must be entered accurately to prevent the motor from damage as a result of overload. The technical specifications of the A90 series inverter are shown in Table 1-2.
Table 1-2 Technical Specifications of A90 Series Inverter 11 A90-4T253 132 253 290 A90-4T304 160 304 340 Items Specifications Three-phase 340V-10% to 460V+10%, Power Rated voltage of Single phase 200V-10% to 240V+10%; supply power supply 50-60Hz ± 5%; voltage unbalance rate: Maximum output The maximum output voltage is the same as the input voltage power voltage. Rated output Continuous output of 100% rated current current Heavy-duty model: Output 150% rated current: 60s; 180% rated current: 10s; 200% Maximum rated current: 2s overload current Light-duty model: 120% rated current: 60s; 150% rated current: 10s; 180% rated current: