User Manual of A90 Series Inverter Pre-output Valid Invalid Positive logic output Active Inactive level Negative logic output Inactive level level Active level Fig. 7-14 Schematic Diagram of Positive and Negative Logic Output of Digital Output The multi-function digital output terminal has two output logics according to the Terminal design: 0: Positive logic. When the function is enabled, the multi-function output terminal will output the active level; otherwise, the multi-function output terminal will output the inactive level. 1: Negative logic.

When the function is enabled, the multi-function output terminal will output the inactive level; otherwise, the multi-function output terminal will output the active level. description of the function code F03.08 . This function code is subject to bit operation. For specific settings, refer to the ★ This function is for logic matching with other external devices. Active level: Y1, low level by default; R1, high level by default. It is usually not necessary for DO to output certain statuses during jog running. The corresponding output can be shielded by setting the corresponding bit of this function code to 1.

If F03.08=xxx1x is set and the FAR output is valid, the actually selected output 156 Function Default Function code name Parameter description Unit Attribute code setting F03.08 Output status control in jogging D7 D6 D5 D4 D3 D2 D1 D0 00000 ○ * * * REV FDT2 FDT1 FAR RUN 0: valid in jogging 1: invalid in jogging