User Manual of A90 Series Inverter Precautions for setting: ★ The start and stop in multi-segment speed operation depends on the function code ★ The acceleration/deceleration time in multi-segment speed operation can be F00.02. controlled by the external terminal with the acceleration/deceleration time The direction of multi-segment speed operation is controlled by the terminals F/R and function. RUN. In addition to the multi-segment speed mode, it also has the simple PLC function. There are four running modes in total, as detailed in Table 7-11.

Table 7-11 Details of PLC Running Mode 190 14 Valid Valid Invalid Valid Multi-segment speed 13 F08.12 15 Valid Valid Valid Invalid Multi-segment speed 14 F08.13 16 Valid Valid Valid Valid Multi-segment speed 15 F08.14 Function Function code Default Parameter description Unit Attribute code name setting F08.15 Simple PLC running mode 0: stop after a single run 1: stop after a limited number of cycles 2: run at the last segment after a limited number of cycles 3: continuous cycles 0 ● F08.16 Limited number of cycles 1 - 10000 1 ● F08.15 Description 0 The inverter will be stopped after running in the last segment. 1 The inverter will run cyclically and be stopped after the set cycles.

The number of cycles depends on the function code F08.16. 2 The inverter will run cyclically and keep the speed of the last segment after running in the last segment, until a stop command is received. The number of cycles depends on the function code F08.16. 3 The inverter will continue cyclic operation until a stop command is received.