User Manual of A90 Series Inverter percentage is directly given, and the maximum output is 100.00%. F09.00=4:VP In the case of 09.00=4VP, the PID setting source is the digital potentiometer setting. F09.00=6: communication setting The percentage of PID setting depends directly on the communication (percentage). If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific setting percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%, as detailed in Table 0-2.
For the general communication (F10.05=0), the specific setting percentage is “7004H (communication setting of process PID setting)”, and the 7004H data range is -100.00% to 100.00%, as detailed in Table 0-2. F09.02=1:AI1 F09.02=2:AI2 The PID feedback percentage is directly dependent on the AI (percentage). For the details of AI1 to AI2, see the description of F00.04. When it is used as the PID feedback, the percentage will directly turn the feedback value, and the maximum output is 100.00%. F09.02=6: communication setting The PID feedback percentage is directly dependent on the communication (percentage).
If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific feedback percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%, as detailed in For the general communication (F10.05=0), the specific feedback percentage is Table 0-2. 200 Default Function code Function code name Parameter description Unit Attribute setting F09.02 PID feedback source 1: AI1 2: AI2 6: Communication setting 1 ○