User Manual of A90 Series Inverter time of torque control. The motor speed can be changed gently by setting the acceleration and deceleration F13.06 represents the time for the torque current to rise from 0 to the rated torque current or fall from the rated current to 0. F13.08=0: depending on F13.09 The upper frequency limit depends on F13.09 during torque control. F13.08=1:AI1 F13.08=2:AI2 The upper frequency limit in torque control is AI (percentage) * F13.09. For the details of AI1 and AI2, refer to the F00.04 description. They have the same meaning.

100.00% is the percentage to the set value of F13.09 (upper frequency limit of 226 Valid Valid Multi-segment torque 4 F13.05 Function Default setting Function code name Parameter description Unit Attribute code F13.06 Torque control acceleration and deceleration time 0.00 - 120.00 s 0.05 ● Function Default Function code name Parameter description Unit Attribute code setting F13.08 Upper frequency limit options of torque control 0: set by F13.09 1: AI1 2: AI2 6: communication percentage setting 7:

direct communication setting 0 ○ F13.09 Upper frequency limit of torque control 0.00 to maximum frequency F00.16 Hz 50.00 ● F13.10 Upper frequency limit offset 0.00 to maximum frequency F00.16 Hz 0.00 ● F13.18 Reverse speed limit options 0 - 100 % 100 ● F13.19 Speed priority enabling of torque control 0: Disable 1: Enable 1 ●