User Manual of A90 Series Inverter 285 7019H to 71FFH Reserved 7200H status word 1 Bit7 to 0 running status 00H Parameter setting 01H Slave running 02H JOG running 03H Self-learning running 04H Slave stop 05H JOG stop 06H Fault status 07H Factory self-inspection 08H - 0FFH Reserved Bit15 to 8 fault information 00H Normal running of inverter xxH Inverter fault status, where “xx” is the fault code 7201H status word 2 Bit0 setting direction 1 - setting is valid 0 + setting is valid Bit1 running direction 1 Reverse frequency output 0 Forward frequency output Working status Bit3 to 2 running mode 00 Speed control mode 7200H 01 Torque control mode ~ 10 Reserved 73FFH 11 Reserved Bit4 parameter protection 1 Valid parameter protection 0 Invalid parameter protection Bit6 - 5 Reserved Bit8 to 7 setting mode 00 Keyboard control 01 Terminal control 10 Communication control 11 Reserved Bit9 Reserved Bit10 warning 0 No warning 1 Warning status (see 7230H for details) Bit15 - 10 Reserved 7202H monitoring frequency +/- Bit0 Output frequency Bit1 Input frequency Bit2 Synchronization frequency