User Manual of A90 Series Inverter 3) Command word for change of set frequency (e.g. 50.00Hz/1388H) (F00.04=7) Send: 01 41 70 15 13 88 3B 97 Return: 01 41 70 15 13 88 3B 97 (normal) Return: 01 C1 04 70 53 (exception, assuming a slave fault) 1) Read the information of the last fault (read the function codes F19.00 to F19.05). Send: 01 03 13 00 00 06 C1 4C Return: 01 03 0C 00 11 00 00 00 00 01 2C 00 00 00 0053 5B (normal) Return:

01 83 04 40 F3 (exception, assuming a slave fault) 298 Send the invoice to Normal Return Exception Return * Frame header ≥3.5 characters (idle) 1 Address 01 Address 01 Address 01 2 Function code 41 Function code 41 Function code C1 3 Register address 70 Register address Hi 70 Exception code 04 (assumption) Hi 4 Register address 15 Register address Lo 15 CRC check Lo 70 Lo 5 Register value Hi 13 Register value Hi 13 CRC check Hi 53 6 Register value 88 Register value Lo 88 Lo 7 CRC check Lo 3 B CRC check Lo 3B 8 CRC check Hi 97 CRC check Hi 97 * Tail ≥3.5 characters (idle) Send the invoice to Normal Return Exception Return * Frame header ≥3.5 characters (idle) 1 Address 01 Address 01 Address 01 2 Function code 03 Function code 03 Function code 83 3 Starting address 13 Number of bytes 0C Exception code 04 (assumption) Hi 4 Starting address 00 Register value Hi 00 CRC check Lo 40 Lo (F19.00) 5 Number (Hi) of 00 Register value Lo 11 CRC check Hi F3 registers (F19.00) 6 Number (Lo) of 06 Register value Hi 00 registers (F19.01) 7 CRC check Lo C Register value Lo 00 (F19.01)