sinee — Руководство по эксплуатации Inverter A90 от SINEE (EN)

User Manual of A90 Series Inverter 3.2.7 Ground wire  The ground terminal must be grounded.  Pay special attention to the third type of grounding (grounding resistance: less than 10Ω).  The ground wire must not be shared by the welding machine and power devices.  Select the ground wire according to the technical specifications for electrical equipment, and minimize the length of the ground wire connected to the grounding point.  Where two or more inverters are used, the ground wires must not form a loop. The correct and incorrect grounding methods are shown in Fig. 3-10.

Inverter Inverter Inverter Inverter Inverter Inverter 3.2.8 Installation and wiring of braking resistor and braking unit Fig. 3-10 Connection of Ground Wire Refer to 0 for the selection and wiring of the braking resistor and braking unit. For the inverter with a built-in braking unit, connect the braking resistor between the inverter terminal (+) and PB terminal. For the inverter with no built-in braking unit, connect the terminals (+ and -) of the braking unit to those (+ and -) of the DC bus of the inverter, and the braking resistor to the PB+ and PB- terminals of the braking unit. Refer to the user manual of the BR100 braking unit for more information.

3.3 Wiring of Control Circuit Terminal 37