User Manual of A90 Series Inverter tightening torque should be 0.5N.m. 3.3.9 Precautions for control circuit wiring  Connect the control circuit connection wires and other wires separately.  Connect the control circuit terminals EA, EB, EC, and Y1 separately from other control circuit terminals.  In order to avoid malfunction caused by interference, use the twisted shielded cables in the control circuit. The wiring distance should be less than 50 m.  Prevent the shield screen from contact with other signal lines and enclosures. The exposed shield screen can be wrapped with insulating tapes.

 It is prohibited to touch the ports and components of the control panel without static electricity protection measures. 44