sinee — A90 User Manual

User Manual of A90 Series Inverter 66 4: VP (keyboard potentiometer) 5: retention 6: percent setting of auxiliary frequency communication 7: direct setting of auxiliary frequency communication 8: retention 9: retention 10: process PID 11: simple PLC F00.06 Options of frequency source 0: main frequency source A 1: auxiliary frequency source B 2: main and auxiliary operation results 3: switching between main frequency source A and auxiliary frequency source B 4: switching between main frequency source A and main and auxiliary operation results 5:

switching between auxiliary frequency source B and main and auxiliary operation results 0 ○ F00.07 Digital frequency setting 0.00 to maximum frequency F00.16 Hz 00.00 ● F00.08 Options of main and auxiliary operation 0: main frequency source A + auxiliary frequency source B 1: main frequency source A - auxiliary frequency source B 2: larger value of main and auxiliary frequency sources 3: smaller value of main and auxiliary frequency sources 0 ○ F00.09 Reference options of auxiliary frequency source B in main and auxiliary operation 0: relative to he maximum frequency 1:

Relative to main frequency source A 0 ○ F00.10 Gain of main frequency source 0.0~300.0 % 100.0 ● F00.11 Gain of auxiliary frequency source 0.0~300.0 % 100.0 ● F00.12 Synthetic gain of main and auxiliary 0.0~300.0 % 100.0 ●