Delta Electronics AH — MC_MoveAbsolute

AH Motion Controller – Motion Control Instructions Manual *Note: _3 1. When one MC_MoveAbsolute instruction is executed but not finished yet, it is invalid to re-execute the instruction.  Outputs  Outputs Update Timing 3-44 Name Function Data type ( Setting value Timing for updating Default value) modulo/rotary axis. 4: mcCurrentDirection (1) BufferMode Specifies the buffering behavior of the instruction. eMC BUFF _ ER MODE* _ 0: mcAborting 1: mcBuffered 2: mcBlendingLow 3: mcBlendingPrevious 4: mcBlendingNext 5: mcBlendingHigh (0) When Execute shifts to True and Busy is False. Name Function Data type Output range (Default value) Done True when absolute target position is reached.

BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Active True when the axis is being controlled. BOOL True/False (False) CommandAborted True when the instruction is aborted. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code when the error occurs. Refer to Appendices for error code descriptions. DWORD 16#0~16#FFFFFFFF (0) Name Timing for shifting to True Timing for shifting to False Done  When the absolute positioning is completed.  When Execute shifts to False.  If Execute is False and Done shifts to True, Done will be True for only one period and immediately shift to False.

Busy  When Execute changes to True.  When Done shifts to True.  When Error shifts to True.  When CommandAborted shifts to True. Active  When the motion on the axis is started  When Done shifts to True.  When Error shifts to True  When CommandAborted shifts to True.