AH Motion Controller – Motion Control Instructions Manual *Note: 1. Refer to Section 2.4 Data Type Unit (DUT): ENUM for explanation on using enumerations. Outputs _3 Outputs Update Timing 3-82 Name Function Data type Output range (Default value) InVelocity True when the specified target velocity is reached. BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Active True when the axis is being controlled. BOOL True/False (False) CommandAborted True when the instruction is aborted. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code if an error occurs.
Refer to Appendices for error code descriptions. DWORD 16#0~16#FFFFFFFF (0) Name Timing for shifting to True Timing for shifting to False InVelocity When the specified target velocity is reached. When CommandAborted shifts to True When CommandAborted shifts to True and the target velocity is changed. Busy When Execute shifts to True. When Error shifts to True. When CommandAborted shifts to True. Active When the motion on the axis is started. When Error shifts to True. When CommandAborted shifts to True. CommandAborted When this instruction is aborted by another instruction with the Buffer Mode set to mcAborting.
When this instruction is aborted because of the execution of MC Stop _ instruction. When Execute changes to False. If Execute is False and CommandAborted shifts to True, it will be True for only one period and immediately shift to False. Error/ErrorID When an error occurs in the execution conditions or input values for the instruction.(Error code is recorded) When Execute shifts from True to False. (Error code is cleared)