Delta Electronics AH — MC_ReadActualTorque

Chapter 3 Motion Control Instructions MC_ReadActualTorque 1. The output Valid is True when the output Torque is valid. If Enable is reset, the data loses its validity, and all outputs are reset. In this case, to update new velocity data requires enabling this instruction again. 2. The reported value of the actual torque at the output is obtained from the servo drive and the unit of the torque value 3_ is the same as that of the servo drive.  Inputs  Outputs 3-125 FB/FC Description FB This instruction reports the axis torque continuously when Enable is set.

Name Function Data type Setting value Timing for updating (Default value) Enable Obtains the value of the outputs continuously while enabled. BOOL True/False (False) - Name Function Data type Output range (Default value) Valid True when the axis torque at the output is available. BOOL True/False (False) Busy Indicates there are incoming new output values and the instruction is not yet finished. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code if an error occurs. Refer to Appendices for error code descriptions. DWORD 16#0~16#FFFFFFFF (0) Torque The value of the actual torque or force (unit:

refer to 6077 hex from the object dictionary of the slave) LREAL refer to 6077 hex from the object dictionary of the slave for the available range or use 0 (0)